Desarrollo de la migración del sistema basado en el PLC PCD3.M3330 por el PLC S7-1214C en el proceso de recepción de pesca en una planta de congelados
Average rating
Cast your vote
You can rate an item by clicking the amount of stars they wish to award to this item.
When enough users have cast their vote on this item, the average rating will also be shown.
Star rating
Your vote was cast
Thank you for your feedback
Thank you for your feedback
Advisors
Nieves Acosta, Ayrton KrickstIssue Date
2025-11-30Keywords
Migración de PLCTIA Portal
Modbus RTU
S7IsoTCP
Yaskawa J1000
HMI Beijer
EPLAN
S7-1200
Modernización industrial
PLC migration
Beijer HMI
Industrial modernization
Metadata
Show full item recordOther Titles
Development of the system migration from the PCD3.M3330 PLC to the S7-1214C PLC for the fish receiving process at a frozen products plantAbstract
Una planta de Chimbote operaba con un PLC Saia PCD3.M3330, una HMI Beijer X2 pro 15 y quince variadores Yaskawa J1000 por RS-485/Modbus RTU en la línea de recepción de pesca. La obsolescencia del sistema y el soporte local motivaron la migración a un PLC Siemens S7-1214C, manteniendo el hardware de campo y la filosofía de operación. El trabajo describe el respaldo del programa original, la traducción de la lógica a bloques FC/FB/DB en TIA Portal, la configuración de la comunicación Modbus RTU mediante el módulo CM1241, el remapeo de variables de la HMI hacia bloques de datos del nuevo PLC y la actualización de planos en EPLAN. Asimismo, se ejecutaron pruebas en planta apoyadas en listas de verificación FAT y SAT. Como resultado, se migraron las 64 entradas y 64 salidas digitales, se mantuvo comunicación estable con los quince variadores y se completaron siete listas de verificación FAT/SAT que cubren paros de emergencia, fallas de comunicación y respaldo de horas de operación. Para el periodo enero–octubre, las horas de parada no planificada asociadas al sistema de control se redujeron de 113,5 h a 90,8 h por campaña, es decir, 22,7 h menos (≈20 %). Considerando un margen de contribución promedio de 820 USD/h, las pérdidas estimadas disminuyen de 93 070 a 74 456 USD por campaña, con un ahorro de 18 614 USD.A frozen products plant in Chimbote originally used a Saia PCD3.M3330 PLC, a Beijer X2 pro 15 HMI and fifteen Yaskawa J1000 VFDs over RS-485/Modbus RTU to control the fish receiving line. System obsolescence and limited local support motivated migration to a Siemens S7-1214C PLC while preserving field hardware and the existing operating philosophy. This work describes the backup of the original program, the translation of the control logic into FC/FB/DB blocks in TIA Portal, the configuration of Modbus RTU communication through a CM1241 module, the remapping of HMI variables to data blocks of the new PLC and the update of drawings in EPLAN. In addition, on-site tests were executed using FAT and SAT checklists. As a result, 64 digital inputs and 64 digital outputs were migrated, stable communication with the fifteen drives was maintained and seven FAT/SAT test checklists were completed, covering zoned emergency stops, communication-loss handling and backup of runtime hours. For the January–October period, unplanned downtime associated with the control system decreased from 113.5 h to 90.8 h per campaign, i.e. 22.7 h less (≈20 %). Assuming an average contribution margin of 820 USD/h, estimated losses decreased from 93 070 to 74 456 USD per campaign, yielding savings of 18 614 USD.